ADAM-6060-CE CIRCUIT MODULE, 6 Relay Output/6 DI Module

  1. Remote monitoring and control with smart phone/pad
  2. Group configuration capability for multiple module setup
  3. Flexible user-defined Modbus address
  4. Intelligent control ability by Peer-to-Peer and GCL function
  5. Multiple protocol support: Modbus TCP, TCP/IP, UDP, HTTP, DHCP
  6. System configuration backup
  7. User Access Control
  8. 10/100 Mbps communication rate
  9. 2000VRMS optical isolation
Please visit via PC to place order/quote
Contact us for stock info
Request Quantity Discount
Features
 
Communication
Ethernet Ports 1 (10/100 Base-TX)
Peer-to-Peer Function Supported
Graphic Control Logic (GCL) Function Supported
Actively Data Transfer Function Supported
Supported Protocol Modbus/TPC, TPC/IP, UDP, HTTP, DHCP
Software
Supported Web Language XML, HTML 5, Java Script
Supported Programming Language VB and C#
OPC Server Software Supported
Watchdog Function System (1.6 second), Communication (programmable
Relay Output
Channels 6
Relay Type Form A (SPST, Normally Open)
Contact Rating 0.5 A @ 120 VAC,1 A @ 30 VDC
Insulation resistance Minimum 1 GΩ @ 500 VDC
Relay On/Off Time (Typical) Relay Off: 3 ms
Relay On: 7 ms
Operating Speed Up to 20 operation/minute (with load)
Breakdown Voltage 500 VAC (50/60 Hz)
Pulse Output Supported
Digital Input
Channels 6
LED Display for Digital Input Status Supported
Input Level Dry Contact:
Logic level 0: close to GND
Logic level 1: open
Wet Contact:
Logic level 0: 0 - 3 V
Logic level 1: 10 - 30 V
Counter Input Function Event Counting, Frequency Measurement
Counter Resolution 32-bit + 1-bit overflow
Counter Input Frequency 0.2 Hz ~ 3 KHz
Counter Function: Keeps the Count Value Supported
Inverted DI Status Supported
Environment
Connector 9P Terminal Block x 1, 13P Terminal Block x 1 (Screw Locking)
Power Input 10 - 30 VDC
LED Display for Power On Status Supported
Power Consumption 3 Watt @ 24 VDC
Dimension 70 x 122 x 27 mm
Isolation Protection 2000 VDC
Power Reversal Supported
Mounting Wall mount, Din-Rail mount, Stack mount
Operating Temperature -20 ~ 70°C (-4 ~ 158°F)
Storage Temperature -30 ~ 80°C (-22 ~ 176°F)
Operating Humidity 20 ~ 95% RH (non-condensing)
Storage Humidity 0 ~ 95% RH (non-condensing)
ADAM-6017
ADAM-6017
8-ch Analog Input and 2-ch Digital Output DAQ Module
Buy more
ADAM-6050
ADAM-6050
18-ch Digital Input and Output DAQ Module
Buy more
EKI-5525
EKI-5525
5-port Industrial-grade SCADA Ethernet Switch
Buy more
Specifications
Category
Attribute
Value
Counter/Encoder Input
Channels
8
Counter/Encoder Input
Max. Input Frequency
3 kHz