Contact Advantech Search Shopping list
  1. 00800-2426-8080
  2. Login
Order By Part Number

ADAM-4150-B Phase out 15-Channel Digital I/O Module

  1. Communication Interface: RS-485, Micro USB, Passive UHF RFID
  2. 7 input channels and 8 output channels
  3. Broader Operating Temperature Range
  4. Higher Noise Immunity: 4 kV surge protection on power inputs, 4 kV EFT, and 8 kV ESD protection
  5. Broader Power Input Range: +10 ~ +48 VDC
  6. LED display allows to monitor the status address settings
  7. Digital Filter Function
  8. DI channels can be used as 1 kVGz counters
  9. Over current/ short circuit protection
Certifications
modbus icon_UL FCC RoHS CE
Please visit via PC to place order/quote
Contact us for stock info
Request Quantity Discount
Please Select Purchase Qty X
Please Select Purchase Qty X
Features
    1. ADAM RS-485 I/O Modules: Simple, Stable, Flexible.

  • The ADAM-4000/ 4100 series featuring rugged industrial-grad cases are specially designed for reliable operation in harsh environments. Built-in microprocessors independently provide intelligent signal conditioning, analog I/O, digital I/O, data display, and RS-485 communication through Modbus protocols.
  • The most used protocol for Industrial Automation development

    1. The new ADAM-4000/ 4100 series modules feature Modbus/RTU as a best remote data transmission protocol.
      Standardized protocol
      • One of the most widely used standard communication protocols for eAutomation development
      Centralized control
      • As an universal remote I/O modules to operate with system via Modbus
      Easy for integration
      • Provides the sample code and command for users to program
  • Non-stop monitoring with Watchdog Timer and protection

    1. For stable and constant performance, ADAM-4000/ 4100 features a Watchdog Timer and maximum protection to ensure the highest level of system reliability.
      Noise protection
      • Data accuracy assured by enhanced ESD / EFT / Surge Protection
      Module stability ensure
      • Once a problem is detected, the Watchdog Timer automatically recovers the system
      Save maintenance costs
      • Watchdog Timer enhances system stability and reduces the maintenance cost
  • Various interfaces to meet your needs

    1. Integration with embedded systems or PLC systems via USB or RS-485.
      Friendly L-shape cable design *
      • Users can optionally order the 90 degree micro USB to a Type-A USB cable with a locking mechanism to provide a stable connection
      Micro USB interface *
      • The new ADAM-4100 series can be powered and transmit data via micro USB interface
      * Only featured on B version of ADAM-4100 series selected models.
  • Efficient management

    1. Now, you can access ADAM-4100 series modules (B version) by passive RFID for more efficient management.
      Quickly obtain module status
      • Quickly retrieve module information (I/O value, alarm event, and etc.) via the RFID interface
      Easy maintenance
      • Recorded RFID tag information (model name, serial number, user defined information, etc.) makes module field maintenance easy
  • ADAM 4000 / 4100 series comparison

        1. Model
        2. ADMA-4000 Series
        3. ADMA-4100 Series
        1. Operation temperature
        2. -10~70°C
        3. -45~85°C
        1. Power input
        2. 10~30VDC
        3. 10~48VDC
        1. RS-485 interface
        2. Support
        3. Support
        1. Micro USB interface
        2. n/a
        3. Support
        1. Built-in RFID tag
        2. n/a
        3. Support
  • Product Dimensions and Packing Information

    1. Product Dimensions
    2. Unit: mm
      Mounting
      • Advantech ADAM series provides various mounting methods to fit the varying needs of different projects in the field.
    1. Opening the Box
Specifications
Category
Attribute
Value
General
Connectors
2 x 10-pin plug-in screw terminal
General
Protocol
ASCII command, Modbus/RTU
Hardware
Certification
CE, FCC
Communications
Interface
RS-485, Micro USB
Counter/Encoder Input
Channels
2
Counter/Encoder Input
Counting Range
32-bit
Counter/Encoder Input
Max. Input Frequency
3 kHz
Isolated Digital Input
Channels
7
Isolated Digital Input
Input Voltage
Dry contact Logic level 0: close to GND, Logic level 1: open. Wet Contact Logic level 0: 0~3 VDC, Logic level 1: 10~30 VDC
Environment
Isolation Voltage
3,000 VDC
Environment
Operating Temperature
-40~85 °C (-40~185 °F)
Isolated Digital Output
Channels
8
Isolated Digital Output
Output Type
Sink
Isolated Digital Output
Output Voltage
0~40 VDC
Isolated Digital Output
Sink Current
800 mA max./channel
Power Requirements
Input Voltage
10~48 VDC
x
Contact Us

00800-2426-8080

Monday-Friday 09-12pm and 13-17pm (CET)