| Communication |
| Communication Baud Rate |
1200 bps - 115.2 kbps |
| Communication Distance |
1200 meters |
| Protocol |
ASCII Command, Modbus/RTU |
| Asynchronous Data Format) |
1 start bit, 8 data bits, 1 or 2 stop bit,
parity check (none, odd, even) |
| Data Flow Function |
Supported |
| Sofeware |
| Programming language support |
VB & C# |
| OPC Server Software |
Supported |
| Watchdog |
System(1.6 sec), Communications (Programmable settings) |
| Analog Input
|
| Analog Input channels |
8 (differential) |
| Resolution |
16-bit |
| Sampling Rate |
10 or100 sample / second (total, selected by utility software)
|
| Input Type |
Voltage, Current
|
| Range |
Voltage: ±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V, ±15 V
0 ~ 150 mV, 0 ~ 500 mV, 0 ~ 1 V, 0 ~ 5 V, 0 ~ 10 V, 0 ~ 15V
Current: 0 ~ 20 mA, 4 ~ 20 mA, ±20 mA |
| Each channel with Different input type and range |
Supported |
| Accuracy |
Voltage: ±0.1% of FSR (Under 25°C condition)
Electric current: ±0.2% of FSR (Under 25°C condition) |
| Impedance |
Voltage Input: 800 kΩ
Current Input: 120 Ω |
| Common Mode |
200 VDC |
| CMR (Under 50/60 Hz condition) |
92 dB |
| NMR (Under 50/60 Hz condition) |
60 dB |
| Span Drift |
± 25 ppm/°C |
| Zero Drift |
± 6 µV/°C |
| Burn-out Detection |
Supported (For current input) |
| Input Over-Voltage Protection |
± 60 VDC |
| Isolation Protection |
3000 VDC |
| Environment |
| Connector |
10P terminal block (screw locking) |
| Power Input |
10 - 48 VDC |
| LED Display Power Status |
Supported |
| Power Consumption |
1.2 Watt @ 24 VDC |
| Dimension |
70 x 122 x 27 mm |
| TVS/ESD Protection |
Supported |
| Power Reversal |
Supported |
| Mounting |
Wall mount , Din-Rail mount, Stack mount |
| Operating Temperature |
-40 ~ 85°C (-40 ~ 185°F) |
| Storage Temperature |
-40 ~ 85°C (-40 ~ 185°F) |
| Operating Humidity |
5 ~ 95% RH (non-condensing) |